It a 1995 air handler , I lost 24 volts to the thermstat . I have 240 into the handler and out the breakers to the transformer . I need advice and parts .Moms a diabetic and we are almost broke . I can buy parts and fix it , I need some advice :)

Asked by Mark on 08/01/2010 1  Answer

ManualsOnline posted an answer 14 years, 4 months ago

The ManualsOnline team has found the manual for this product! We hope it helps solve your problem. Get the Manual Here
0 check the transformer to see if you have 24 volts out on it. If not then it's the transformer thats bad. If you do follow the 24 volt wires toill u no longer have voltage. if u have voltage untill u leave the furnace cabinet then pull new wires to the stat