pinnacle performance. the water won't heat up.

Asked by Joe on 06/22/2014 1  Answer

ManualsOnline posted an answer 10 years, 5 months ago

The ManualsOnline team has found the manual for this product! We hope it helps solve your problem. Get the Manual Here
5 Possible Causes Sudden Change: Improper water level Gradual Change: Mineral deposits in boiler and heat exchanger Possible Repairs Check reading of the Tridicator (combination pressure / temperature gage). If water pressure is low (below 12 psi) the system needs to have water added. The boiler's automatic filling system using the pressure relief valve should maintain proper water level by maintaining a 12-15 psi pressure. If you do not have a pressure reducing valve you can also manually feed the boiler by opening up the water feed valve until boiler pressure reaches 12 psi. If problem arose gradually then the cause may be due to deposits in the system. Flush the boiler or call a service technician for this task. Expansion tank may have too much or too little water. It must be properly charged with air to prevent boiling.