Conettix D6600/D6100 | Computer Interface Manual | 3.0 Computer Communication Protocols
.
Bosch Security Systems, Inc. | 1/07 | 4998122703-01 23
Table 27: Silent Knight Automation Format
To Automation
Report Code Description
2 5 16=0(EEZZ) 2 5 16=1(ZZ)
Note
00: Alarm Panic PAss 00
01 to 08: Alarm 01 to 08 sA0x 01 to 08 x=1 to 8
09: Holdup Hass 09
10 to 19: Alarm 10 to 19 sA1x 10 to 19 x=0 to 9
20 to 29: Alarm Restore 10 to 19 sH1x 20 to 29 x=0 to 9
30: Test Code sXss 30
31: Trouble Line 1 LT01 31
32: Trouble Line 2 LT02 32
33: Expand Trouble ETss 33
34: Forced Access DFss 34
35: Restore Line 1 LR01 35
36: Restore Line 2 LR02 36
37: Expand Restore ERss 37
38: Cancel Code OCss 38
39: Data Lost RTss 39
40: Closing CL00 40
41 to 49: Closing 01 to 09 CL0x 41 to 49 x=1 to 9
50 to 59: Bypass 10 to 19 sB1x 50 to 59 x=0 to 9
60: Trouble AC ATss 60
61 to 68: Trouble 01 to 08 sT0x 61 to 68 x=1 to 8
69: Trouble BAT YTss 69
70: Restore AC ARss 70
71 to 78: Restore 01 to 08 sRss 71 to 78
79: Restore BAT YRss 79
80: Access DS00 80
81 to 89: Access 01 to 09 DG0x 80 to 89 x=1 to 9
90: Opening OP00 90
91 to 99: Opening 01 to 09 OP0x 91 to 99