Warning!
Operating the input as an analog input between 0.5 V and 5 V might cause abnormal results.
This input state is not defined and might change expected results.
Notice!
Reverse configuration is not for use in UL Listed applications.
Automation Link Monitoring (COM3) through CPU Programmable Output
Ports
The output connections on the I/O port have an open collector transistor output that can
activate an external sounder or light if the automation system fails.
Notice!
Configure external devices using the specifications listed in the table below. Outputs are not
verified by UL.
Radionics D6615 CPU Terminator Card Bosch D6615 CPU Terminator C
Solid state output provides a current sink to
common (-)
Solid State output provides a current sink to
common (-)
Maximum load is 20 mA Maximum load is 75 mA
Vsat @ 1 mA = 0.5 VDC Vsat @ 10 mA = 0.5 VDC
Vsat @ 10 mA = 3.0 VDC Vsat @ 25 mA = 1.0 VDC
Maximum voltage = 30 VDC Vsat @ 50 mA = 2.5 VDC
Maximum voltage = 30 VDC
Table 10.1: Terminator Card Configuration
10.1.2
32 en | Input and Output Ports
Conettix Communications Receiver/
Gateway
2012.11 | 08 | 4998122704 Installation and Operation Guide Bosch Security Systems, Inc.