Power Supply — Electrical characteristics of available
power supply must agree with unit nameplate rating. Supply
voltage must be within limits shown in Table 3.
IMPORTANT: Operating unit on improper supply volt-
age, or with excessivephase imbalance, constitutes abuse
and may affect Carrier warranty. SeeUnbalanced 3-Phase
Supply Voltage, page 7.
Power Wiring All power wiring must comply with
applicable local andnational codes. Install field-supplied branch
circuit fused disconnect(s) per NEC (National Electrical Code,
U.S.A.) of a type that can be locked OFF or OPEN. Dis-
connect(s) must be within sight from and readily accessible
from unit in compliance with NEC Article 440-14.
GENERAL WIRING NOTES
1. A crankcase heater is wired in the control circuit so it is
always operable as long as power supply disconnect is
on, even if any safety device is open or unit stop-start
switch is off. It is protected by a 5-amp circuit breaker in
control power.
2. The power circuit field supply disconnect should never be
open except when unit is being serviced or is to be down
for a prolonged period. When operation is resumed, crank-
case heater should be energized for 24 hours before start-
up. If unit is to be shut down for a prolonged period, it
is recommended that the suction and discharge valves be
closed to prevent an excessive accumulation of refriger-
ant in the compressor oil.
3. Power entry is one end only.
4. Maximum field wire sizes allowed by lugs on terminal
block are:
UNIT
38AKS
V-Ph-Hz
WIRE
SIZE*
028 208/230-3-60
350 kcmil
034
208/230-3-60
230-3-50
044
208/230-3-60
230-3-50
LEGEND
AWG American Wire Gage
kcmil Thousand Circular Mils
*All other units use 2/0 AWG (67.4 mm
2
).
5. Terminals for field power supply are suitable for copper,
copper-clad aluminum, or aluminum conductors. Insula-
tion must be rated 167 F (75 C) minimum.
CONDENSER FANS — The fans must rotate counterclock-
wise when viewed from above. If necessary, correct direc-
tion of fan rotation by interchanging any 2 power input wires
at disconnect switch. Affix crankcase heater decal (located
in installer’s packet) to unit disconnect switch.
Table 3 Electrical Data
60 HZ
UNIT
38AKS
UNIT COMPRESSOR FAN MOTORS
Volts
3 Ph, 60 Hz
Supplied*
MCA
MOCP
(Fuse)
ICF RLA LRA FLA (ea) Qty
Min. Max.
028
500
200
600
100
208/230
380
460
575
187
342
414
518
254
418
508
632
124.6
64.7
60.7
52.5
200
110
100
80
452.2
250.9
226.1
167.4
89.8
45.5
43.6
36.5
446
247
223
164
6.2
3.9
3.1
3.4
2
2
2
2
034
500
200
600
100
208/230
380
460
575
187
342
414
518
254
418
508
632
145.5
72.5
68.7
54.9
250
125
110
90
512.2
283.9
256.1
179.4
106.5
52.6
50.0
38.5
506
280
253
176
6.2
3.9
3.1
3.4
2
2
2
2
044
500
200
600
100
230
380
460
575
187
342
414
518
254
418
508
632
203.0
111.1
91.0
81.5
350
175
150
125
702.4
389.8
351.2
282.8
147.5
79.5
65.4
57.1
690
382
345
276
6.2
3.9
3.1
3.4
3
3
3
3
50 HZ
UNIT
38AKS
UNIT COMPRESSOR FAN MOTORS
Volts
3 Ph, 50 Hz
Supplied*
MCA
MOCP
(Fuse)
ICF RLA LRA FLA (ea) Qty
Min. Max.
028
800
300
900
230
346
400
198
311
342
254
380
400
109.0
64.9
60.5
175
100
100
348.4
263.4
226.0
76.9
44.9
43.6
342
259
223
6.4
4.4
3.0
2
2
2
034
800
300
900
230
346
400
198
311
342
254
380
400
120.2
76.1
68.5
200
125
110
372.4
298.4
256.0
85.9
53.9
50.0
366
294
253
6.4
4.4
3.0
2
2
2
044
800
300
900
230
346
400
198
311
342
254
380
400
150.6
112.6
90.8
250
175
150
557.8
408.8
351.0
105.1
79.5
65.4
545
400
345
6.4
4.4
3.0
3
3
3
LEGEND
CSA Canadian Standards Association
FLA Full Load Amps
ICF MaximumInstantaneousCurrent Flowduring starting(thepoint
in thestartingsequence wherethe sumof theLRAforthe start-
ing compressor, plus the total FLAfor all runningfan motors is
maximum).
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (complies with National
Electrical Code [NEC, U.S.A.], Section 430-24)
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
UL Underwriters’ Laboratories
*Units are suitable for use on electrical systems where voltage sup-
plied tounitterminals isnot beloworabove listedminimum andmaxi-
mum limits.
6