16
Table 3 — Electrical Data--50HE (cont)
UNIT
SIZE
NOMINAL
V ---PH--- Hz
IFM
TYPE
CONV
OUTLET
VOLTAGE
RANGE
COMPRESSOR(each) OUTDOORFAN
IFM
FLA
ELECTRIC HEAT POWERS UPPLY DISCONNECTSIZE
Min Max QTY RLA LRA QTY FLA
CRHEATER
--- ---A00 or
B00
Actual kW{ FLA MCA MOCP** FLA LRA
006
(tons)
460--- 3--- 60
STD
NO 414 508 1 8.4 70.0 1 0.8 2.6
NONE — — 13.9 20.0 14.0 92.0
006A00 5.5 7.2 13.9 20.0 14.0 92.0
008A00 10.6 13.8 20.5 25.0 19.0 92.0
009A00 12.9 16.8 24.3 25.0 22.0 92.0
008,008 21.1 27.7 37.8 40.0 35.0 92.0
008,009 23.4 30.1 40.8 45 38 92
YES 414 508 1 8.4 70.0 1 0.8 2.6
NONE — — 16.6 20.0 16.0 94.0
006A00 5.5 7.2 16.6 20.0 16.0 95.0
008A00 10.6 13.8 23.9 25.0 21.0 95.0
009A00 12.9 16.8 27.7 30.0 25.0 95.0
008,008 21.1 27.7 41.2 45.0 37.0 95.0
008,009 23.4 30.1 44.2 45 40 95
HS
NO 414 508 1 8.4 70.0 1 0.8 3.4
NONE — — 14.7 20.0 14.0 101.0
006A00 5.5 7.2 14.7 20.0 14.0 102.0
008A00 10.6 13.8 21.5 25.0 20.0 102.0
009A00 12.9 16.8 25.3 30.0 23.0 102.0
008,008 21.1 27.7 38.8 40.0 36.0 102.0
008,009 23.4 30.1 41.8 45 38 102
YES 414 508 1 8.4 70.0 1 0.8 3.4
NONE — — 17.4 20.0 17.0 104.0
006A00 5.5 7.2 17.4 20.0 17.0 104.0
008A00 10.6 13.8 24.9 25.0 22.0 104.0
009A00 12.9 16.8 28.7 30.0 26.0 104.0
008,008 21.1 27.7 42.2 45.0 38.0 104.0
008,009 23.4 30.1 45.2 50 41 104
006
(tons)
575--- 3--- 60
STD
NO
518 632 1 7.1 53.0 1 0.6 2.0
NONE — — 11.5 15 11 65
YES NONE — — 13.6 15 13 67
HS
NO
518 632 1 7.1 53.0 1 0.6 2.8
NONE — — 12.3 15 12 74
YES NONE — — 14.4 20 14 76
Humidi-
Mi$er
NO
518 632 1 7.1 53.0 1 0.8 3.4
NONE — — 12.2 15 12 78
YES NONE — — 14.4 20 14 80
FLA ---FullLoadAmps
HACR --- Heating,AirConditioningandR efrigeration
IFM ---In door(Evaporator)FanMotor
LRA --- LockedRotorAmps
MCA ---Minimum CircuitAmps
MOCP --- Maximum Overcurrent Protection
NEC --- NationalElectricalCode
OFM ---Outdoor(Condenser)FanMotor
RLA --- RatedLoadAmps
NOTES:
* Thevalueslistedinthistabledonotincludepowerexhaust. Seepowerexhausttableforpowerexhaustrequirements.
**Fuse orHACRbreaker
{Heatercapacity(kW)isbasedon heatervoltageof240v,480vor575v. Ifpowerdistributionvoltage tounitvaries fromratedheatervoltage,heaterkWwillvary accordingly
50HE,HJ