Table 15 — Complete C Control LED Code and
Fault Descriptions
LEGEND
Table 16 — Aquazone™ Deluxe D Control Current LED Status and Alarm Relay Operations
LEGEND NOTES:
1. If there is no fault in memory, the Fault LED will flash code 1.
2. Codes will be displayed with a 10-second Fault LED pause.
3. Slow flash is 1 flash every 2 seconds.
4. Fast flash is 2 flashes every 1 second.
5. EXAMPLE: “Flashing Code 2 is represented by 2 fast flashes fol-
lowed by a 10-second pause. This sequence will repeat continually
until the fault is cleared.
SERVICE
Perform the procedures outlined below periodically, as
indicated.
LED
CODE
FAULT DESCRIPTION
1 No fault in memory There has been no fault since the last power-down to power-up sequence
2 High-Pressure Switch HP open instantly
3 Low-Pressure Switch LP open for 30 continuous seconds before or during a call (bypassed for first 60 seconds)
4 Freeze Protection Coax — FP1 FP1 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
5 Freeze Protection Air Coil — FP2 FP2 below Temp limit for 30 continuous seconds (bypassed for first 60 seconds of operation)
6 Condensate overflow Sense overflow (grounded) for 30 continuous seconds
7
(Autoreset)
Over/Under Voltage Shutdown "R" power supply is <19VAC or >30VAC
8 PM Warning Performance Monitor Warning has occurred.
9 FP1 and FP2 Thermistors are swapped FP1 temperature is higher than FP2 in heating/test mode, or FP2 temperature is higher than FP1 in cooling/
test mode.
FP Freeze Protection
HP High Pressure
LED Light-Emitting Diode
LP Low Pressure
PM Performance Monitor
DESCRIPTION
STATUS LED
(Green)
TEST LED
(Yellow)
FAULT LED (Red) ALARM RELAY
Normal Mode On Off Flash Last Fault Code in Memory Open
Normal Mode with PM On Off Flashing Code 8
Cycle (closed 5 sec,
open 25 sec, …)
Deluxe D Control is
non-functional
Off Off Off Open
Test Mode On Flash Last Fault Code in Memory Cycling Appropriate Code
Night Setback Flashing Code 2 Flash Last Fault Code in Memory
ESD Flashing Code 3 Flash Last Fault Code in Memory
Invalid T-stat Inputs Flashing Code 4 Flash Last Fault Code in Memory
No Fault in Memory On Off Flashing Code 1 Open
HP Fault Slow Flash Off Flashing Code 2 Open
LP Fault Slow Flash Off Flashing Code 3 Open
FP1 Fault Slow Flash Off Flashing Code 4 Open
FP2 Fault Slow Flash Off Flashing Code 5 Open
CO Fault Slow Flash Off Flashing Code 6 Open
Over/Under Voltage Slow Flash Off Flashing Code 7 Open (closed after 15 minutes)
HP Lockout Fast Flash Off Flashing Code 2 Closed
LP Lockout Fast Flash Off Flashing Code 3 Closed
FP1 Lockout Fast Flash Off Flashing Code 4 Closed
FP2 Lockout Fast Flash Off Flashing Code 5 Closed
CO Lockout Fast Flash Off Flashing Code 6 Closed
CO Condensate Overflow
ESD Emergency Shutdown
FP Freeze Protection
HP High Pressure
LP Low Pressure
PM Performance Monitor
IMPORTANT: When a compressor is removed from this
unit, system refrigerant circuit oil will remain in the com-
pressor. To avoid leakage of compressor oil, the refrigerant
lines of the compressor must be sealed after it is removed.
IMPORTANT: All refrigerant discharged from this unit
must be recovered without exception. Technicians must fol-
low industry accepted guidelines and all local, state and fed-
eral statutes for the recovery and disposal of refrigerants.
IMPORTANT: To avoid the release of refrigerant into the
atmosphere, the refrigerant circuit of this unit must only be
serviced by technicians which meet local, state and federal
proficiency requirements.
IMPORTANT: To prevent injury or death due to electrical
shock or contact with moving parts, open unit disconnect
switch before servicing unit.