![](https://pdfstore-manualsonline.prod.a.ki/pdfasset/b/26/b2611106-a72d-4698-807e-ddf4b368d188/b2611106-a72d-4698-807e-ddf4b368d188-bg22.png)
34
Table 10 – LEDs
The LEDs on the RTU--MP show the status of certain functions
If this LED is on... Status is...
Power The RTU MP has power
Rx The RTU MP is receiving data from the network segment
Tx The RTU MP is transmitting data over the network segment
DO# The digital output is active
The Run and Error LEDs indicate control module and network status
If Run LED shows...
And Error LED shows... Status is...
2 flashes per second Off Normal
2 flashes per second
2flashes,
alternating with Run LED
Five minute auto---restart delay after system error
2 flashes per second
3flashes,
then off
Control module has just been formatted
2 flashes per second
4flashes,
then pause
Two or more devices on this network have the
same ARC156 network address
2 flashes per second On
Exec halted after frequent system errors or
control programs halted
5 flashes per second On Exec start---up aborted, Boot is running
5 flashes per second Off Firmware transfer in progress, Boot is running
7 flashes per second
7 flashes per second, alternating with
Run LED
Ten second recovery period after brownout
14 flashes per second
14 flashes per second,
alternating with Run LED
Brownout
On On
Failure. Try the following solutions:
S Turn the RTU---MP off, then on.
S F o rmat t h e R TU --- M P.
S Download memory to the RTU---MP.
S Replace the RTU---MP.
NOTE: Refer to Form 48--50H--T--2T for complete
configuration of RTU--MP, operating sequences and
troubleshooting information. Refer to RTU--MP 3rd Party
Integration Guide for details on configuration and
troubleshooting of connected networks. Have a copy of
these manuals available at unit start--up.
50TC