The raceway provides the UL required clearance between
high-- and low--voltage wiring. Pass the control wires
through the hole provided in the corner post, then feed the
wires thorough the raceway to the RTU--MP. Connect to
the wires to the removable Phoenix connectors and the n
reconne ct the connectors to the board.
Space Temperature (SPT) Sensors
A field--supplied Carrier space temperature sensor is
required with the RTU --MP to monitor space temperature.
There are 3 sensors available for this application:
S 33ZCT55SPT, space tempe r ature sensor with override
button
S 33ZCT56SPT, space tempe r ature sensor with override
button and setpoint a djustment
S 33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment
Use 20 gauge wire to connect the sensor to the controller.
The wire is suitable for distances of up to 500 ft. Use a
three--conductor shielded cable for the sensor and setpoint
adjustment connections. If the setpoint adjustment
(slidebar) is not required, then an unshielded, 18 or 20
gauge, two--conduct or, twisted pair cable may be used.
Connect T--55 -- See Fig. 31 for typical T--55 interna l
connec tions. Connect the T--55 SEN terminals to
RTU--MP J20--1 and J20--2. See Fig. 50.
SEN
SEN
J20-1
J20-2
C08460
Fig. 50 -- RTU--MP T--55 Sensor Connections
Connect T--56 -- See Fig. 33 for T--56 internal
connec tions. Install a jumper between SEN and SET
terminals as illustrated. Connect T--56 terminals to
RTU--MP J20--1, J20--2 and J20--3 per Fig. 51.
SEN J20-1
J20-2
SEN
SET
Jumper
J20-3
SET
C08461
Fig. 51 -- RTU--MP T--56 Sensor Connections
Connect T --59 -- The T--59 space sensor requires a
separat e, isolated power supply of 24 VAC. See Fig. 51
for internal connections at the T--59. Connect the SEN
terminal (BLU) to RTU--MP J20--1. Connect the COM
terminal (BRN) to J20--2. Connect the SET terminal (STO
or BLK) to J20--3.
OR SET SEN
OPB COM- PWR+
BLU (SPT)
BLK (STO)
24 VAC
SENSOR
WIRING
POWER
WIRING
BRN (COM)
NOTE: Must use a separate isolated transformer.
C07132
Fig. 5 2 -- Space Temperature Sensor Typical Wiring
(33ZCT59SPT)
Economizer controls
Outdoor Air Enthalpy Control (PNO HH57AC077) --
The enthalpy cont rol (HH57AC077) is available as a
field--installed accessory to be used with the E conoMi$er2
dampe r system. The out door air enthalpy sensor is part of
the enthalpy control. (The separate field--installed
accessory return air enthalpy sensor (HH57AC078) is
required for di fferential enthalpy control. See Return Air
Enthalpy Sensor”below.)
Loca te the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harness and connect
these leads to enthalpy control sensors 2 and 3. See
Fig. 36. Connect the enthalpy control power input
terminals to economizer actuator power leads RED
(connec t to TR) and BLK (connect to TR1).
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
Differential Entha lpy Control Differential enthalpy
control is provided by sensing and compa ring the outside
air and return air enthalpy conditions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
Return Air Enthalpy Sensor Mount the return--air
entha lpy sensor (HH57AC078) in the return --air duct. The
return air sensor is wired to the enthalpy controller
(HH57AC077). See Fig. 37.
To wire the return a ir enthalpy sensor, perform the
following:
1. Use a 2--c onductor, 18 or 20 AWG, twisted pair ca ble
to connec t the return air enthalpy sensor to the enthal-
py controller.
2. At the enthalpy control remove the factory --installed
resistor from the (SR) and (+) terminals.
3. Connect the field--supplied RED wire to (+) spade
connec tor on the return air e nthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air