CONDITION POSSIBLE CAUSE
REMEDY/
REFERENCE
SECTION
5.14 COMPRESSOR OPERATING IN REVERSE
CAUTION
Allowing the scroll compressor to operate in reverse for more than two minutes will result in internal
compr e ssor damage. Turn the start--stop switch OFF immediately.
Incorrect wiring of compressor
Electrical
Incorrect wiring of compressor contactor(s)
Check
Incorrect wiring of current sensor
5.15 ABNORMAL TEMPERATURES
Discharge temperature sensor drifting high Replace
Failed economizer, TXV or solenoid valve Replace
High discharge temperature
Plugged economizer, TXV or solenoid valve Replace
Loose or insufficiently clamped sensor Replace
Failed liquid injection solenoid valve Replace
Discharge temperature sensor drifting low Replace
o
suction temperature
Loose or insufficiently clamped sensor Replace
5.16 ABNORMAL CURRENTS
Unit reads abnormal currents Current sensor wiring Check