21
Power cord is 55 in. (1,4 m) long and extends from
bottom of control panel. See Step 24, if power cord
must be relocated to opposite side of unit. Do NOT
use a plug adapter or extension cord.
NOTE
o
The Reset button must be pushed in for proper
operation.
o
The power supply cord must be replaced if it
fails to trip when the test button is pressed or
fails to reset.
o
Do not use the power supply cord as an off/on
switch. The power supply cord is designed as a
protective device.
o
A damaged power supply cord must be replaced
with a new power supply cord obtained from the
product manufacturer and must not be repaired.
o
The power supply cord contains no use
serviceable parts. Opening the tamper-resistant
case voids all warranty and performance claims.
NOTES
To test your power supply cord:
1. Plug power supply cord into a grounded 3-prong outlet.
2. Press RESET.
3. Press TEST (listen for click; Reset button will trip and pop out)
4. Press and release RESET (listen for click; Reset button will latch and
remain in). The power supply cord is ready for operation.
POWER SUPPLY CORD
This room air conditioner is equipped with a power supply
cord required by UL (Underwriters Laboratories). This power
supply cord contains state-of-the-art electronics that sense
leakage current. If the cord is crushed, the electronics detect
leakage current and power will be disconnected in a fraction
of a second.