Specifications
In This Section
Environmental Specifications.....................................................................................................105
Server Specifications ..................................................................................................................105
Environmental Specifications
Temperature range* Specification
Operating
10°C to 35°C (50°F to 95°F)
Shipping
-40°C to 60°C (-40°F to 140°F)
Storage -20°C to 60°C (-4 to 140°C)
Maximum wet bulb temperature
30°C (86°F)
Relative humidity
(noncondensing)**
Specification
Operating 10% to 90%
Shipping 10% to 90%
Storage 10% to 95%
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m
(1.8°F per 1,000 ft) to 3048 m (10,000 ft) is applicable. No direct sunlight allowed. Upper
operating limit is 3,048m (10,000 ft) or 70 Kpa/10.1 psia. Upper non-operating limit is
9,144 m (30,000 ft) or 30.3 KPa/4.4 psia.
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C
(113°F). Altitude maximum for storage corresponds to a pressure minimum of 70 KPa.
Server Specifications
Dimensions Specifications
Height 4.29 cm (1.69 in)
Depth 71.1 cm (28.00 in)