Overview 6
Overview
UPS R7000 overview
The HP UPS R7000 features a 4U rackmount design and offers power protection for loads up to 7200
VA/7200 W (NA/JPN) or 6500 VA/6500 W (INTL).
UPS R7000 features
Features include:
• 4U UPS height, 3U ERM height
• ERM technology that uses advanced battery management to increase battery service life, optimize
recharge time, and provide a warning before the end of useful battery life
• Extended runtime with up to four ERMs per UPS
• Easily replaceable battery modules that simplify maintenance
• Emergency shutdown control through the REPO port
• HP UPS Network Module network connectivity with monitoring and control
• Firmware that is service upgradeable through the standard DB-9 communication port
• Backed by worldwide agency approvals
To benefit from the latest product enhancements, update to the latest versions of UPS firmware and software.
NOTE: To download the latest versions of UPS firmware and software, see the HP website
(http://www.hp.com/go/rackandpower).
Important safety information
WARNING: To reduce the risk of fire, only connect unit input to a circuit provided with branch
circuit overcurrent protection for 40 A rating in accordance with the National Electric Code,
ANSI/NFPA 70.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove the source
from the ground.
WARNING: Contact with any part of a grounded battery can result in electrical shock. Shock risk
is reduced if grounds are removed during installation and maintenance.