A SERVICE OF

logo

Programming Master Programming Level
92 MS-9200UDLS PN 52750:A 11/04/05
3.6.5.6 Relays
Pressing 3 while viewing System Setup Screen #2 will allow the programmer to
configure two of the three main circuit board Form-C relays. The following screen
will be displayed:
To program Relay 1 or Relay 3, press the number corresponding to the selected
relay. Note that Relay 2 is fixed as a Trouble relay. Selecting Relay 2 will have no
effect on its programming. The following screen will appear for each relay to be
programmed:
Pressing 1 for Type while viewing the Relay Screen will cause the following
screens to be displayed:
While viewing the selected screen, press the number corresponding to the desired
relay type to program the main circuit board relay. The choice will be stored in
memory and the display will return to the Relay Type Screen which will show the
programmed type choice. Press the Escape key to return to the Relays Selection
Screen and repeat the preceding procedure for the remaining relays.
Note: AR in SUPERVISORY AR and PROCMON AR indicates AutoResettable
which means that the relay will not latch when either of these conditions occur. If
the corresponding condition is cleared, the relay will return to its normal state
without the necessity of resetting the control panel.
SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
RELAYS
1=RELAY 1
2=RELAY 2
3=RELAY 3
Relays Selection Screen
RELAY #
1=TYPE
ALARM
Relay Type Screen
RELAY
1=ALARM
2=SUPERVISORY
3=SUPERVISORY AR
Relay Screen #1
RELAY
1=TROUBLE
2=COMM FAIL
3=PROCESS-MON
Relay Screen #2
RELAY
1=PROCMON AR
2=AC LOSS
3=HAZARD
Relay Screen #3
RELAY
1=MEDICAL
Relay Screen #4