Master Programming Level Programming
MS-9200UDLS PN 52750:A 11/04/05 97
If an ACS annunciator is installed, press 1 while viewing Annunciator Screen #2 to
select addresses for the ACS annunciators. The following screen will be displayed:
Pressing the down arrow key will allow the programmer to view additional screens
displaying Addresses 1 -31. To select one or more addresses for the installed ACS
annunciator(s), press the number key corresponding to the address in each screen.
The display for the selected address will change from No to Yes. Each press of the
number key will cause the display to toggle between No and Yes.
3.6.9.2 Onboard DACT
The Onboard DACT (Digital Alarm Communicator/Transmitter) provides
communication to a central station. Pressing 2 while viewing the Option Module
Screen will cause the following screens to be displayed:
3.6.9.2.1 Onboard DACT Enable
To enable the onboard DACT, press 1 while viewing Onboard DACT Screen #1
until the display reads Enabled Yes. The display will toggle between Enabled Yes
and Enabled No with each press of the key.
ANNUNCIATOR
1=ADDRESS 1 YES
2=ADDRESS 2 NO
3=ADDRESS 3 NO
ACS Installed Screen
OPTION MODULES
1=ANNUNCIATORS/UDACT
2=ON BOARD DACT
3=PRINTER/PC
Option Module Screen
ON BOARD DACT
1=ENABLED YES
2=PRIMARY PHONE
3=SECONDARY PHONE
On Board DACT Screen #1
ON BOARD DACT
1=SERVICE TERMINAL
2=CENTRAL STATION
3=MANUAL DIAL MODE
On Board DACT Screen #2