Page14
7039-131H
May 5, 2011
R
2100 Millennium Wood Stove (ACC)
NOTE: InCanadawhenusingafactory-builtchimneyitmust
besafetylisted, Type UL103 HT (2100
o
F) CLASS “A” or
conformingtoCAN/ULC-S629M, STANDARD FOR 650
o
C
FACTORY-BUILT CHIMNEYS.
5
Chimney Requirements
Floor
Protector
Chimney
Connector
Insulated " T "
Flashing
Listed Termination Cap
Trim Collar on
Inside Wall
Listed Chimney
Storm Collar
Wall Support
Roof Brace (if required)
Thimble
Floor
Protector
Chimney
Connector
Ceiling Support
Listed Chimney
Listed Termination Cap
Storm Collar
Flashing
Figure 14.1 Prefabricated Exterior Chimney
Figure 14.2 - Prefabricated Interior Chimney
A. Venting Components
Chimney Connector:
Itisalsoknownasuepipeorstovepipe.Thechimney
connectorjoinsthestovetothechimney.Itmustbea6inch
(152mm)minimumdiameter24gaugemildsteelblackor
26gaugebluedsteel,oranapprovedair-insulateddouble
wallventingpipe.
Thimble:
A manufactured orsite-constructed device installed in
combustible wallsthroughwhichthe chimney connector
passes to the chimney. It is intended to keep the walls
from igniting. Site constructed thimbles must meet
NFPA 211 Standards. Prefabricated must be suitable
for usewith selectedchimney andmeetUL103 Type HT
Standards.Followinstructionsprovidedbythemanufacturer
for manufactured thimbles for masonry chimney and
prefabricatedchimneys.
Chimney:
Thechimneycanbeneworexisting,masonryorprefabricated
andmustmeetthefollowingminimumrequirementsspecied
inSection5B.
B. Chimney Systems
• Must beminimum 6 inch(152mm) diameter (ID)high
temperaturechimneylistedtoUL103HT(2100
o
F)or
ULCS629M.
• Mustusecomponentsrequiredbythemanufacturerfor
installation.
• Mustmaintainclearancesrequiredbythemanufacturer
forinstallation.
• Refertomanufacturersinstructionsforinstallation.
Prefabricated Metal Chimney