Catalog No.: 2000.312D Effective: 11-15-07 Replaces: 1-1-07
Hi Delta – Type H
Models 992B-2342B Model
SPECIFICATIONS
A
pprox.
MBTUH Firing
A
H
K
TW
A
mp. Shipping
Model Input Output Stages Width NPT
Draw* Wt. (Lbs.)
992B 990 832 3 57-1/8 2-1/2 10 10 16-13/16 <12 900
1262B 1260 1058 4 68-1/2 2-1/2 12 10
20-9/16
<12 1010
1532B 1530 1285 4 79-7/8 2-1/2 12 10
24-3/8
<12 1225
1802B 1800 1512 4 91-1/8 2-1/2 14 10
28-1/8
<12 1350
2002B 1999 1679 4 102-1/2 2-1/2 14 10
31-15/16
<12 1450
2072B 2070 1739 4 102-1/2 2-1/2 14 10
31-15/16
<12 1450
2342B 2340 1966 4 113-7/8 2-1/2 16 10
35-11/16
<12 1520
Dimensions are in inches. * Without pump
RATES OF FLOW AND PRESSURE DROPS
20°F T 30°F T
Min. Flow Max. Flow
Model GPM
P (ft)
GPM
P (ft)
GPM
P (ft) T
GPM
P (ft) T
992B 84 5.6 56 2.5 42 1.5 40 132 14.0 13
1262B 107 10.0
71
4.5 53 2.6 40 132 15.5 16
1532B 130
16.0
86
7.1 65 4.1 40 132 16.5 20
1802B N/A N/A
102
10.8 76 6.0 40 132 18.0 23
2002B N/A N/A
113
14.0 85 8.1 40 132 19.5 26
2072B N/A N/A
117
15.0 88 8.7 40 132 19.5 27
2342B N/A N/A
132
21.0 99 12.0 40 132 21.0 30
Basis is 30 GPM or 40°F T for minimum flow, 132 GPM for maximum flow.
NOTE: Pump location
varies based on model
and application
NOTES: 1. Rates shown are for natural or propane gas, and elevations up to 5,000 feet. For installation above 5,000 feet, please contact manufacturer.
2. Required natural gas pressure is 7 – 10.5” WC. Required propane gas pressure is 11 - 13” WC.
Raypak, Inc. 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 Fax (800) 872-9725 www.raypak.com