Setup Instructions
IMPORTANT!
The pump must
be running
when adding
oil.
IMPORTANT!
For maximum
performance,
change the
vacuum pump
oil frequently.
NOTE: The vacuum pump is shipped without oil in the reservoir. Before starting
the pump, oil must be added to the pump, or damage to the pump may occur.
5. Press the START key to begin the oil fill process.
6. Attach the flexible tube and cap to the oil bottle, and pour eight ounces of
vacuum pump oil into the fill port.
7. Press the START key. While the vacuum pump is running, slowly add oil
until the level rises to the center of the reservoir's sight glass.
8. Press the STOP key, and replace the black plastic plug on the fill port.
9. Connect the service hoses, open both panel valves, and press START.
10. Connect the fill hose to a full source tank.
11. Open the tank valve. Invert the tank and install it on the back of the unit,
making sure to secure the tank strap.
NOTE: If using a refillable tank, install the tank upside down, and connect the fill
hose to the vapor valve.
INST0947
1
2
3
1. Oil Fill
2. Sight Glass
3. Oil Drain
12. Press START, and the unit will automatically run a
five-minute vacuum to clear all internal air.
13. After the vacuum is complete, press START to begin
filling the internal storage vessel.
14. The unit stops when a sufficient amount of refrigerant
has been transferred to the internal tank, or when the
source tank is empty. Press the STOP key to pause the
process. Press STOP again to exit, or START to
resume. This process takes 15-20 minutes.
NOTE: Add at least 8 lb. (3.6 kg) of refrigerant before
stopping the process to ensure enough refrigerant is available
for charging.
15. When the fill process is complete, you may press STOP
to exit.
16. The unit is now ready to operate.
NOTE: There is no need to calibrate the scale, because it is
calibrated at the factory.