Regulates brownouts as low as 89V back to usable levels without consuming battery power
4 UPS battery-supported/surge-protected outlets plus 4 additional surge suppression-only outlets
USB port and PowerAlert software enables unattended shutdown in case of extended power failure
HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X.
PowerAlert Software available via free download from www.tripplite.com
650VA/350W power handling ability supports a variety of sensitive computer, home theater and other equipment
3.5 min. full load runtime (650VA/350W), 12 min. half-load runtime (325VA/175W)
Cabinet adapts to tower format or rackmount shelf format. Rackmount (2U) format requires an optional shelf, available separately
2-year product warranty
$200,000 connected equipment insurance (USA & Canada Only).
Specifications
SYSTEM OVERVIEW
Voltage compatibility 120
Frequency
compatibility
60
OUTPUT
Output VA 650
Output watts 350
Output nominal
voltage
120VAC
Output voltage
regulation
BATTERY MODE: PWM sine wave 115V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity / type 8 NEMA 5-15R
INPUT
Maximum input amps 12A
Input connection type NEMA 5-15P (right-angle plug)
Input cord length 6 ft./1.8 m
Recommended
Electrical Service
120V 15A
BATTERY
Full load runtime 3.5 min. (650VA/350W)
Half load runtime 12 min. (325VA /175W)
DC system voltage 12VDC
Typical battery
lifespan
4-6 years (depending on usage)
Battery recharge rate 2-8 hours to 90%
VOLTAGE REGULATION
Voltage regulation
description
Line-interactive voltage regulation corrects brownouts as low as 89V back to usable values
Brownout correction Input voltages between 89V and 104V are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs Front panel LCD screen with blue backlight offers continuous input line voltage data, plus UPS status information on
line power status, battery power status, battery charge level and voltage regulation operation
Alarms Audible alarm with 15-second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front
panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain.
Switches Includes 2 front panel switches, one main on/off power switch and one dual-function alarm cancel/self test button
SURGE / NOISE SUPPRESSION