Alert notifications via email or SNMP traps offer immediate event notification
Firmware upgrade ability supports future product enhancements
Supports HTTP, HTTPS, PowerAlert Network Management System, SMTP, SNMPv1, SNMPv2, Telnet, SSH, FTP, DHCP, BOOTP, NTP
protocols
Fully compatible with FREE PowerAlert Network Management System / NMS Software
Included cord retention brackets keep vital network equipment plugged in and continuously powered
Toolless mounting supported in button-mount compatible racks, plus nut-and-bolt mounting brackets for other mounting applications (set of
2 9mm buttons pre-installed, 2 9mm and 4 6mm spare buttons included)
TAA Compliant Version Available - Order Tripp Lite PDU3VN10G60WTAA
Specifications
OVERVIEW
PDU Type Monitored
OUTPUT
Output Capacity Details 12.6kVA total; 20A per bank (balanced)
Frequency compatibility 60 Hz
Output nominal voltage 208V single phase
Overload protection 3 20A double-pole circuit breakers (1 per output phase)
Outlet quantity / type 36 total - 30 C13 (10 per phase), 6 C19 (2 per phase)
Outlet Type IEC-C13, IEC-C19
INPUT
PDU Input Voltage 208
Maximum Input Amps (A) 35
PDU Plug Type IEC-309 60A BLUE (3P+E)
Input cord length (ft.) 10
Input cord length (m) 3.05
Phase 3-Phase
LEDS ALARMS & SWITCHES
Switches Pushbutton switches enable local display of each phase separately, display rotate and display IP address
functions
Front panel LEDs 2 digit current meter display reports output amps per phase and IP address
PHYSICAL
Shipping Dimensions
(HWD/in)
6.6 x 9.3 x 75.5
Shipping Dimensions
(HWD/cm)
16.8 x 23.6 x 191.8
Shipping weight (lbs) 24.3
Shipping weight (kg) 11
Unit Dimensions (HWD/in) 70 x 2.19 x 1.76
Unit Dimensions
(HWD/cm)
177.8 x 5.6 x 4.47
Unit weight (lbs) 17.1