DC system
voltage
36 V DC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge
rate
2-4 hours to 90%
Replacement
Battery Cartridge
RBC53
VOLTAGE REGULATION
Voltage
regulation
description
Automatic Voltage Regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without using
battery power, during brownouts to 75V and overvoltages to 147V
Overvoltage
correction
Input voltages between 128 and 147V AC are reduced by 12%
Direct pass
through
Input voltages between 108 and 127V AC are passed on to connected equipment unchanged
Brownout
correction
Input voltages between 93 and 107V AC are boosted by 14%
Severe brownout
correction
Input voltages between 75 and 92V AC are boosted by 30%
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 5 front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION
STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information
Alarms Audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous short beeps) and
low battery (continuous tone)
Switches Yes, includes 2 front panel mounted push-button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge
suppression
480 joules
AC suppression
response time
Instantaneous
EMI / RFI AC
noise
suppression
Yes
PHYSICAL
Shipping weight
(lbs)
42.6
Shipping weight
(kg)
19.4
Unit weight (lbs) 38.4
Unit weight (kg) 17.5
Unit Dimensions
(HWD/in)
12.75 x 7.5 x 9
Unit Dimensions
(HWD/cm)
32.4 x 19.1 x 22.9
Material of
construction
PVC
Form factors
supported
Tower
Cooling method Built-in rear exit cooling fan
Battery Access Battery access door allows hot swap battery replacement without powering connected equipment off
ENVIRONMENTAL