Voltage regulation
description
Automatic voltage regulation (AVR) circuits maintain clean, regulated computer-grade 120V nominal output, without
using battery power, during brownouts to 95V and overvoltages to 145V
Overvoltage
correction
At 120V, input voltages between 127-145V are reduced by 12%
Brownout correction At 120V, input voltages between 95-108V are boosted by 14%
LEDS ALARMS & SWITCHES
Front panel LEDs Includes 10 front panel LEDs to indicate line/battery power status, over/undervoltage correction, battery charge level,
load percentage, overload and replace battery
Alarms Audible alarms indicate BATTERY MODE and OVERLOAD, UPS POWERED ON
Switches 2 front panel mounted switches. POWER ON switch powers UPS on in AC or battery mode when pressed longer than
one second. POWER ON switch also initiates self-test when pressed longer than .5 seconds with the UPS in line power
mode. Also serves as an alarm
SURGE / NOISE SUPPRESSION
AC surge
suppression
738 joules
AC suppression
response time
Instantaneous
Dataline suppression Includes 8-wire RJ45 style jack; pins 1,2,3 & 6 offer 10baseT Ethernet line surge suppression with 7.5V clamping, pins 4
& 5 offer single-line tel/DSL line suppression starting at 260V. (POE Compatible)
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 47.7
Shipping weight (kg) 21.5
Shipping
Dimensions
(HWD/in)
14 x 9.8 x 18.3
Shipping
Dimensions
(HWD/cm)
35.6 x 24.9 x 46.5
Unit weight (lbs) 44.6
Unit weight (kg) 20.1
Unit Dimensions
(HWD/in)
10.1 x 6.65 x 13.75
Unit Dimensions
(HWD/cm)
25.7 x 16.9 x 35
Material of
construction
Steel
Form factors
supported
Tower
Cooling method Fan
Battery Access Supports battery access and hot-swap replacement without powering off connected equipment
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
COMMUNICATIONS
Network monitoring
port
2 built-in monitoring ports: 1 x USB and 1 x DB9. Each supports on battery, low battery, power restored, AC line
voltage, DC battery voltage, load percentage, battery charge current, battery capacity, temperature and line frequency
status messaging.
Software and
cabling included
PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with 2 cables: 1
x USB and 1 x DB9
SNMP compatibility SNMP adapter accessory #SNMPWEBCARD