PowerAlert Software and DB9 serial communications port enable remote monitoring of UPS status and site power conditions; safe
unattended shutdown without data loss during extended power failures; messaging of UPS and line power status: on-battery, low-battery,
power-restored, AC line voltage, DC battery voltage and battery capacity
Communications ports support timed inverter shutoff after unattended shutdown, activate self-test and 10 second reboot of connected
equipment
PowerAlert UPS monitoring and unattended shutdown software with complete cabling included
Battery replacement door
Notification of system status via 5 LEDs and multi-function audible alarms
Wall mountable with user-supplied UPSWM wallmount bracket
Cold start capability enables UPS turn-on in battery mode during blackout conditions
2 year manufacturer's product warranty
$250,000 Ultimate Lifetime Insurance
Specifications
SYSTEM OVERVIEW
Voltage
compatibility
120V AC
Frequency
compatibility
60Hz
OUTPUT
Output VA 700
Output watts 450
Output nominal
voltage
120V AC
Output voltage
regulation
LINE MODE: Sine wave line voltage 120V (-18% / +8%), BATTERY MODE: PWM sine wave output 120V +/-5%
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10% BATTERY MODE: Inverter output regulated to 60Hz +/-0.5Hz
Outlet quantity /
type
6 NEMA 5-15R
Overload
protection
Via 10A input circuit breaker
INPUT
Maximum input
amps
4.33A / 520 watts
Input connection
type
NEMA 5-15P
Input cord length 7 ft., 16 gauge
Recommended
Electrical Service
15A 120V
BATTERY
Full load runtime 6 minutes (700VA)
Half load runtime 20 minutes (350VA)
DC system voltage 12 VDC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge
rate
2-4 hours to 90%
Replacement
Battery Cartridge
RBC52 (quantity 2)