Accepts input voltages between 156 and 276, regulating output within 2% of selected 200/208/220/230/240V nominal voltage
Supports connected equipment during blackouts for 20/8 minutes at half/full load levels. Runtime is further expandable with optional
external battery packs
Network interfaces support simultaneous communications via 2 DB9 ports and SNMPWEBCARD slot
Included PowerAlert UPS monitoring software supports safe unattended shutdown, monitoring and control via local connected servers, plus
any number of additional servers over IP
Communications ports support on-battery, low-battery, power-restored, AC-voltage, DC-voltage, output current monitoring, battery charge
current, battery capacity, AC line frequency, timed inverter shutoff, activate self-test and output power control
Built-in Emergency Power Off (EPO) interface with cable
Includes 4 built-in output receptacles (2 L6-30R, 2 L6-20R)
L6-30P input plug-in connection
Front panel LEDs and LCD readout with scroll button enables visual confirmation of all major UPS functions and current site electrical
conditions
Front panel switches enable power on/off control, self-test and alarm cancel functions
Included adjustable mounting rails support installation in 4 post 19 inch rack enclosures. Optional 2POSTRMKITWM supports 2 post
rackmount installation
UPS ships fully assembled in full compliance with DOT regulations, no time consuming connection of internal batteries by user is required
Fault-tolerant auto-bypass maintains continuous utility output to connected equipment, even in cases where the UPS is overloaded or
suffers an internal failure that requires service
2 year manufacturer's product warranty, $250,000 Ultimate Lifetime Insurance (USA & Canada only)
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC (200/208/220/230/240V)
Frequency
compatibility
50/60Hz
OUTPUT
Output VA 5000
Output watts 3500
Output nominal
voltage
208V AC (200/208/220/230/240V)
Output voltage
regulation
Maintains pure sine wave output at all times, regulated within 2% of selected nominal output voltage, less than 5% total
harmonic distortion
Output frequency
regulation
Regulates line frequency to 50/60Hz +/- 0.05Hz
Outlet quantity / type 2 NEMA L6-30R, 2 NEMA L6-20R
Overload protection Resettable circuit breaker
INPUT
Maximum input amps 24A 208V / 21A 240V
Input connection type NEMA L6-30P
Input cord length 10 ft / 3 m
Recommended
Electrical Service
30A at 200, 208, 220, 230, 240V
BATTERY
Full load runtime 8 minutes (5000VA / 3500 watts)
Half load runtime 20 minutes (2500VA / 1750 watts)
Expandable battery
runtime
Yes, with optional external battery packs
DC system voltage 240V DC
Typical battery
lifespan
4-6 years