Electrical Connection
Connection Checklist
Recommended Cable Sizes
Terminal Wiring Diagrams
Parallel Wiring Diagrams
Follow all warnings listed in the Safety section prior to hardwire terminal connection. The following checklist provides a general guide rather than
a complete outline of procedures.
Connection Checklist
Turn off input power prior to electrical connection.
Check the input, output and battery cables for proper amplitude, phase and polarization.
Connect ground wire(s) between UPS power module(s) and battery module(s).
If the input and output power of the UPS is a Y connection, then note that the Neutral wire and Ground wire are not connected within the UPS
power module.
If the input power system has a floating voltage between Neutral and Ground, and if 0 volts is desired between Neutral and Ground within the
UPS power module, Tripp Lite recommends the following: add a user-supplied isolation transformer to the input of the UPS, and connect the
Neutral wire and Ground wire inside the UPS power module.
If installing multiple UPS modules in parallel, ensure input and output cables are the same length for each module.
Recommended Cable Sizes
UPS Power Module
Model SU50K3/3PM SU80K3/3PM SU50K3/3INTPM SU80K3/3INTPM
UPS System Capacity (kVA) 50 80 50 80
Input Circuit Breaker (A) 100 150 125 200
Input Cable (AWG) 2 1/0 1 3/0
Input Cable (mm
2
)225035 70
Reserve Input Circuit Breaker (A) 75 125 100 150
Reserve Input Cable (AWG) 6 2 4 1
Reserve Input Cable (mm
2
)10 25 16 35
Output Circuit Breaker (A) 75 125 100 150
Output Cable (AWG) 6 2 4 1
Output Cable (mm
2
)102516 35
See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Cable Size Information.
Installation
(continued)
Floor Weight Loading Table
UPS Power Module
Model SU50K3/3PM SU80K3/3PM SU50K3/3INTPM SU80K3/3INTPM
UPS System Capacity (kVA) 50 80 50 80
Weight (lb) 1276 1540 1012 1155
Weight (kg) 580 700 460 525
Weight Loading (lb/in
2
) 1716 1495 1361 1554
Weight Loading (kg/m
2
) 1208 1054 958 1094
See Battery Module Owner's Manual or Contact Tripp Lite for Battery Module Weight Loading Information.
Torque Specifications
50kVA Models:
150A Terminal Blocks: 61 kgf/cm (4.4 ft/lb)
200A Terminal Blocks: 102 kgf/cm (7.5 ft/lb)
80kVA Models:
200A Terminal Blocks: 102 kgf/cm (7.5 ft/lb)