A SERVICE OF

logo

Familiarize yourself with the location and function of the front and rear panel
features before installing and operating your UPS.
FRONT
PANEL
0
0
0
0
UPS
SYSTEM
,
5
1.
"ON/OFFn Switch:
This momentary rocker switch turns the UPS System's inverter
ON and OFF.
2.
"SELECT" Button:
This button performs two functions: it allows you to browse
through different power readings on the LCD Display by momentarily pressing the
button; it also allows you to silence the UPS alarm by pressing and holding the button
for
3
seconds.
3.
LCD Display:
This
backlit
(16x2
character) dot matrix display indicates a wide range
of UPS operating conditions and diagnostic data. It will illuminate after you have
properly completed installation and start-up and after the
"ON/OFFm Switch
is
turned
ON.
4.
"I/P (Input) LED:
This green light will illuminate constantly to indicate an AC input
supply
is
present.
5.
"AC/DC" (Converter) LED:
This green light will illuminate constantly to indicate the
UPS's AC/DC converter is activated.
6.
"DC/ACW (Inverter)
LED:
This green light will illuminate constantly to indicate the
UPS's DC/AC inverter
is
activated.
7.
"O/P (Output) LED:
This green light will illuminate constantly to indicate your UPS
is supplying AC power to connected equipment.
8.
"BYPASS" LED:
This green light will illuminate when the UPS
is
providing filtered
mains powerwithout engaging its converter or inverter. Connected equipment will not
receive battery power in the event of a blackout.
9.
"BATTERY" LED:
This red light will illuminate when the UPS
is
discharging the
battery to provide connected equipment with
AC power.
An
alarm
will sound which
can be cancelled by pressing and holding the "SELECT" switch for
3
seconds. The
alarm will be cancelled, but the LED will remain illuminated.