Set 1. Press the “Set” button once and it will display the Set Point. After approximately 5 sec-
onds, the display will return to normal operation and display the Bottle Probe tempera-
ture.
2. Press the “Set” button once and it will display the Set Point. Press the up and down ar-
rows to change the set point. Press the Set button again and the numbers will blink,
conrming the change in Set Point.
3. Press and hold the “Set” button during the display of the Hi/Low “Temperature Data His-
tory” (hold button unit “rst” blinks on display), and it will erase the past recorded data le
and start recording, from the current time and temperature.
4. Press the “Set” and the “Down Arrow” buttons simultaneously, for 3-5 seconds, and you
will access the “Customer Preference Selection Mode” (CPSM). The CPSM allows the cus-
tomer to “Fine Tune” the Control Operating System to their applicable choice.
Alarm The Alarm symbol is shown when the system encounters an issue that needs attention, the
displayed alarm codes are explained below.
Alarm Codes
Message Cause Solution
“P1”
Bottle Probe is Unplugged Attach Bottle Probe to Unit
Faulty Bottle Probe Connection 1. Check Bottle Probe attachment at circular connector
2. Check Bottle Probe connection at green terminal block on
back of controller
Defective Bottle Probe Replace the Bottle Probe
“P2” Faulty Evaporator Probe
Connection
Check Evaporator Probe connection at green terminal block on
back of controller
Defective Evaporator Probe Replace the Evaporator Probe
“HA” Defective Bottle Probe Replace the Bottle Probe
“LA” The Bottle Probe is sensing a
temperature of 4° below the set
point
Allow the room to warm up which will increase the temperature
of the wine
Defective Bottle Probe Replace the Bottle Probe
“POF” The keypad is locked Hold “Up” and “Down” buttons for 3 to 5 seconds to disable,
“PON” should appear