Appendix A: RTU Open Points/Properties
72 RTU Open
BACview:
>
– The value of the Optional SPT (Rnet) sensor. Also allows i-Vu & Field Assistant users access to sensor
configuration. See Carrier Sensors Installation Guide
for additional details.
– Input Channel 1; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space RH.
– Input Channel 2; 4 - 20 mA only. User-configurable for IAQ, OAQ, or Space Relative Humidity.
– Input Channel 6; 10K Thermistor only. Supply Air Temperature.
– Input Channel 7; 10K Thermistor only. Outside Air Temperature.
– Input Channel 10; 10K Thermistor only. Space Temperature (T55, 56, 59).
– Input Channel 11; 100K Potentiometer only. Setpoint adjust (T56, 59).
– Input Channel 11; used to detect an open circuit (faulty Setpoint adjustment mechanism).
– Input Channel 3; Dry Contact only. User-configurable for No Function, Compressor Safety, Fan Status, Filter
Status, Remote Occupancy, or Door Contact.
– Input Channel 4; Dry Contact only. Safety Chain.
– Input Channel 5; Dry Contact only. User-configurable for No Function, Fire Shutdown, Fan Status, Filter
Status, Remote Occupancy, or Door Contact.
– Input Channel 8; Dry Contact only. User-configurable for No Function, Enthalpy, Fan Status, Filter Status,
Remote Occupancy, or Door Contact.
– Input Channel 9; Dry Contact only. User-configurable for No Function, Humidistat, Fan Status, Filter Status,
Remote Occupancy, or Door Contact.
Off = Space Temp valid.
– Reflects the status of the Space Temp (Rnet) input. On = Space Temp invalid,
– Analog Output Channel 1; jumper selectable.
– Analog Output Channel 2; 0 - 10 Vdc. Not Utilized.
– Binary Output 1; Fan (G) Output.
– Binary Output 2; Heat 2 (W2) Output.
– Binary Output 3; Heat 1 (W1) Output.
– Binary Output 4; Cool 2 (Y2) Output.
– Binary Output 5; Cool 1 (Y1) Output.
– Binary Output 6; Humidi-MiZer ™ Output.
– Binary Output 7; Reversing Valve Output.
– Binary Output 8; Power Exhaust Output.