182
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS DEFAULT
CCN TABLE/
SUB-TABLE
CCN POINT PAGE NO.
COOL (cont) Cooling Configuration COOL_CFG 15
B2.FN Level 2 Fans B 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (PG0816)
6 (20, PM16)
2 (2428)
HumidiMizer FIOP:
0 (0314)
1 (PG16)
3 (20, PM16)
2 (2428)
CIR_B_2
B3.FN Level 3 Fans B 0 to 7 no HumidiMiZer
FIOP:
0 (0307)
3 (PG0816)
6 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_B_3
CIR.C Circuit C 19
CC.LO Circuit C Lockout Temp 0 to 100F °F 0 OATLCMPC
CS.C1 Current Sensing C1 Disable/En
able
Disable (0314,
2028)
Enable (PG16)
C1_SENSE
C1.FN Level 1 Fans C 07 no HumidiMiZer
FIOP:
0 (0314)
1 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (PG0316)
1 (2028, PM16)
CIR_C_1
C2.FN Level 2 Fans C 0 to 7 no HumidiMiZer
FIOP:
0 (0314)
3 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
2 (2028, PM16)
CIR_C_2
C3.FN Level 3 Fans C 0 to 7 no HumidiMiZer
FIOP:
0 (0314)
3 (PG16)
0 (2028, PM16)
HumidiMiZer FIOP:
0 (0314)
1 (PG16)
3 (2028, PM16)
CIR_C_3
SST Low Suction Control 39
SST.O Suction OK Temperature 10 to 50 °F 18 SSTOK
SST.1 Low Suction Level 1 10 to 50 °F 20 SSTLEV1
SST.2 Low Suction Level 2 5 to 50 °F 15 SSTLEV2
SST.3 Low Suction Level 3 0 to 50 °F 10 SSTLEV3
CK.DL Delay On Low SST Check 0 to 300 sec 0 SSTCKDLY
OFC Outdoor Fan Control 19
OFC.3 OFC3 Enable. CCH Dis
able
No/Yes No (PG0316)
Yes (2028, PM16)
OFC3_CTL
0.MXP Fan Lev0 Max Pressure 100 to 500 psig 200 LEV0MAXP
1.MXP Fan Lev1 Max Pressure 100 to 500 psig 400 (PG0316)
450 (2028, PM16)
LEV1MAXP
2.MNP Fan Lev2 Min Pressure 100 to 500 psig 150 (PG0316)
200 (2028, PM16)
LEV2MINP
2.ON Fan Lev2 On Temperature 0 to 100 °F no HumidiMiZer
FIOP:
55 (0320)
45 (2428)
HumidiMiZer FIOP:
68 (20, PM16)
61 (2428)(PG0316)
LEV2ON
2.OFF Fan Lev2 Off Temperature 0 to 100 °F no HumidiMiZer
FIOP:
45 (PG0316)
50 (20, PM16)
40 (2428)
HumidiMiZer FIOP:
57 (2028,
PM16)(PG0316)
LEV2OFF
2.MXP Fan Lev2 Max Pressure 100 to 500 psig 400 LEV2MAXP
3.MNP Fan Lev3 Min Pressure 100 to 500 psig 250 LEV3MINP
48/50PG and PM