40 Installation (for qualified installers only)
© Travis Industries 4080214 100-01182_003
Mantel Requirements
• The illustration below details mantel clearances and maximum mantel depth.
• Any material that protrudes more than 3/4” from the non-combustible facing is considered a mantel
and must meet the mantel requirements.
Examples: • If you wish to have a 8” deep mantel, it must be at least 12-1/4” above the fireplace face (49” above the base).
• If you wish to have a mantel 8” above the fireplace face, it must be no deeper than 3-3/4”.
Maximum Mantel Depth (b)
Mantel
Height
Above
Face (a)
0”
1”
2”
8”
7”
6”
5”
4”
3”
9”
0” 1” 2” 3” 4” 5” 6” 7” 8” 9” 10”11”
12”
10”
11”
12”
13”
14”
15”
16”
17”
18+”
36-3/4”
a
b
Base of the Fireplace
Mantel
(combustible or non-combustible)
Combustible mantel columns (legs) that
protrude more than 3/4” from the glass
frame must meet the sidewall clearance. If
they protrude 3/4” or less, they must meet
the facing clearance (2-1/4” from the glass
frame - to the side of the fireplace, not in
front of it).
Non-combustible mantel columns do not
have a minimum clearance.