IPGSM-4GC Trouble Detection Information
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4GC, and Telco 2 is used by the IPGSM-
4GC to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if
there are no faults in the Communicator.
Fault Condition Indication to Fire Panel
PowerBoost1 fault Telco 2 is cut.
Communicator fault
Failure of the communications path when
IP only or GSM only is programmed as a
communications path.
Telco 2 is cut.
Failure of both communications paths
when IP&GSM is programmed as a
communications path.
Telco 1 and 2 are cut.
Dialer Capture Module buffer is full. Hang up. (Panel will retry, giving the buffer a chance
to empty.)
IPGSM-4GC Specifications
ITEM SPECIFICATION
Cabinet Dimensions: Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches
Transformer: 1451-UL9 Primary – 120VAC, 60Hz, 850mA, Secondary – 18VAC, 72VA
Battery: 12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.
Battery Charging Current: maximum 1A
Battery Discharge Current: standby 230mA, active 950mA
Environment: Operating temperature: –20º to +55ºC, for ULC installations 0ºC to
+49ºC
Storage temperature: –40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing, for ULC
installations 0% to 93%
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
Supervision: The Radio (communicator), battery, and AC power, conditions are
monitored by the cabinet indicator LEDs:
RADIO TROUBLE lights when any of these conditions exist.
Both IP and GSM communication paths are lost.
Communicator radio is not registered.
Old Alarm Time has been exceeded. (Message has not been
delivered within the fixed 10 minute window.)
LOW BATTERY lights when the battery voltage is less than 11.5VDC.
AC LOSS lights when the AC power is less than 90VAC.