C
B
D
A
11
STOVE CLEARANCES UNPROTECTED SURFACES PROTECTED SURFACES
TOP VENT/VERTICAL
per NFPA 211 or CAN/CSA-B365-M
SIDE REAR CORNER SIDE REAR CORNER
Rear heatshield with 24" 25" 18" 10" 14" 10"
Single wall pipe 610 mm 635 mm 460 mm 255 mm 355 mm 255 mm
Rear heatshield with 18" 10" 14" 6" 6" 6"
Double wall pipe or shields 460 mm 255 mm 355 mm 150 mm 150 mm 150 mm
STOVE CLEARANCES UNPROTECTED SURFACES PROTECTED SURFACES
REAR VENT/HORIZONTAL per NFPA 211 or CAN/CSA-B365-M
SIDE REAR CORNER SIDE REAR CORNER
Rear heatshield with 24 25 20 10 25 18
Single wall pipe 610 mm 635 mm 510 mm 255 mm 635 mm 460 mm
Rear heatshield with 18 14 17 6 6 6
Double wall pipe or shields 460 mm 355 mm 430 mm 150 mm 150 mm 150 mm
CONNECTOR UNPROTECTED SURFACE PROTECTED SURFACE
CLEARANCES
per NFPA 211 or CAN/CSA-B365-M
Single wall pipe-vertical installations 18" (460mm) 6" (150mm)
Double wall pipe-
vertical installations pipe mfgr. listing pipe mfgr. listing
Single wall pipe-
horizontal installations 18 (460mm) 9 (230mm)
Double wall pipe-horizontal installations pipe mfgr. listing pipe mfgr. listing
VERY IMPORTANT:
Top Vent - Vertical: assumes the connector pipe
runs from the top of the stove and travels vertically.
If top vented to a horizontal run, the stove position
is dictated by the connector pipe clearances.
Rear Vent - Horizontal: assumes the connector
pipe extends from the rear of the stove and travels
horizontally to the chimney. If rear vented to a
vertical run, the stove position is dictated by the
connector pipe clearances.
Dimensions in Inches represent U.S. requirements.
Dimensions in Millimeters represent Canadian
requirements.
WALL PROTECTION IS DISCUSSED IN FURTHER
DETAIL ON PAGE 12 OF THIS MANUAL.
F 3 CB WOODSTOVE CLEARANCES*
MANTEL CLEARANCES
A = Top to Mantel 34 860 mm
B = Top to Top Trim 20 510 mm
C = Side to Side Trim 13 330 mm
D = Side to Side Wall: 24 610 mm