Five total outlets (two L6-20R, one L6-30R and two 5-15R)
Diagnostic LEDs provide visual indication of 17 separate performance conditions
Included PowerAlert Software provides e-mail or pager notification of power problems and simultaneous automatic unattended shutdown of
multiple servers
4 built-in communications ports (2 USB/2 DB9) for remote monitoring and unattended shutdown
Slot for SNMP/web card (part#: SNMPWEBCARD) and environmental sensor (part#: ENVIROSENSE) for remote communications in large
IP environments
Emergency Power Off (EPO) interface for emergency shutoff in large facilities
Hot-swappable/user-replaceable batteries allow on-site battery replacement through the front panel without powering off connected
equipment or removing the UPS from the rack
UPS ships fully assembled and ready for installation; no time-consuming user battery connections required
$250,000 Ultimate Lifetime Insurance. No warranty cards required for coverage!
2-year manufacturer's product warranty
Specifications
SYSTEM OVERVIEW
Voltage compatibility 208V AC
Frequency
compatibility
60 Hz
OUTPUT
Output VA 5000
Output watts 3750
Output nominal
voltage
208V AC
Output voltage
regulation
LINE MODE: Sine wave output within 208V (-6% +20%) plus 120V nominal (600VA max @ 120V)
Output frequency
regulation
LINE MODE: Passes line frequency of 60Hz +/-10%
Outlet quantity / type 1 NEMA L6-30R, 2 NEMA L6-20R and 2 NEMA 5-15R
Overload protection Resettable circuit breaker
INPUT
Maximum input amps 24A / 3970 watts @208V
Input connection type NEMA L6-30P
Input cord length 10 ft., 10 gauge
Recommended
Electrical Service
30A 208V (or 50A 208V)
BATTERY
Full load runtime 8.5 min (5000VA)
Half load runtime 20 min (2500VA)
DC system voltage 48 VDC
Typical battery
lifespan
3-6 years, depending on usage
Battery recharge rate 2-4 hours to 90%
Replacement Battery
Cartridge
RBC94-3U (qty 3)
VOLTAGE REGULATION
Voltage regulation
description
Automatic Voltage Regulation (AVR) circuits maintains clean, regulated computer-grade 208/120V nominal output,
without using battery power, during brownouts to 167V and overvoltages to 260V
Overvoltage
correction
Input voltages between 228V and 260V are reduced by 12%