Brownout correction Input voltages between 167V and 194V are boosted by 12%
LEDS ALARMS & SWITCHES
Front panel LEDs 5 front-panel LEDs: Green POWER LED, Green VOLTAGE CORRECTION LED, 3-color BATTERY CHARGE LED,
3-color OUTPUT LOAD LED, red BATTERY WARNING LED
Alarms 3 function audible alarm indicates power failure conditions (4 short beeps every 10 seconds), overload (continuous
short beeps) and low battery (continuous tone)
Switches Yes, includes 2 front panel mounted push button switches for system enable, self-test and alarm cancel functions
SURGE / NOISE SUPPRESSION
AC surge
suppression
1020 joules
AC suppression
response time
Instantaneous
EMI / RFI AC noise
suppression
Yes
PHYSICAL
Shipping weight (lbs) 181.9
Shipping weight (kg) 82.58
Shipping
Dimensions (HWD/in)
11.25 x 23 x 31.5
Shipping
Dimensions
(HWD/cm)
28.6 x 58.4 x 80
Unit weight (lbs) 143.3
Unit weight (kg) 65.1
Unit Dimensions
(HWD/in)
5.25 x 17.5 x 25
Unit Dimensions
(HWD/cm)
13.3 x 44.5 x 63.5
Material of
construction
Steel
Form factors
supported
Rack (3U)
Cooling method Built-in cooling fan
Battery Access Battery access door allows hot swap battery replacement without powering connected equipment off
ENVIRONMENTAL
Relative Humidity 0 to 95%, non-condensing
Storage Temperature +5 to +122 degrees Fahrenheit
Operating
Temperature
+32 to +104 degrees Fahrenheit
COMMUNICATIONS
Network monitoring
port
Includes built-in USB and DB9 serial ports. Each supports on battery, low battery, power restored, AC line voltage, DC
battery voltage, load percentage, battery charge current, battery capacity, internal UPS temperature and line frequency
status messaging
Software and cabling
included
Includes PowerAlert UPS monitoring software for all common network and standalone operating systems. Ships with
USB and DB9 serial cables
SNMP compatibility Built-in accessory slot accommodates internal SNMP / Web card and other network accessories
WatchDog
compatibility
Yes, compatible with Tripp Lite's Watchdog system service to restore operation to locked equipment through soft reboot
of applications / OS or hard power off/on reboot of connected equipment - ideal for unattended kiosk applications
LINE / BATTERY TRANSFER