Mounting (Tower)
MounttheUPSsysteminanupright,towerpositionusing2-9USTANDbasestands(optional).Theusermustdeterminethefitnessofhardware
andproceduresbeforemounting.
WARNING! The UPS system is extremely heavy. Use caution when lifting and mounting. User must properly stabilize the UPS when
lifting and mounting.
Adjust the stands to a width of 6.93
inches(176mm)foraUPS.Adjustthe
standstoawidthof12.07inches(306.5
mm)foraUPSandanexternalbattery
module.Alignthestandsapproximately
10inches(254mm)apart.Haveoneor
moreassistantshelpyouplacetheUPS
onitssideinthestands.PlacetheUPS
sothat itscontrol panelis ontop and
facingoutward.
RotatetheUPS'scontrolpaneltoview
iteasierwhiletheUPSistowermounted.
Insertasmallscrewdriver,orothertool,
intheslotsoneithersideofthecontrol
panel.Popthepanelout;rotateit;and
popthepanelbackintoplace.
5
Mounting
3
2
1
4
1
2
1 Power Module
6.93" (176 mm)
1 Power Module +
1 Battery Module
12.07" (306.5 mm)
1 Power Module
6.93" (176 mm)
1 Power Module +
1 Battery Module
12.07" (306.5 mm)
1
1
I/P BYPASS
BATTERY AC/DC DC/AC
O/P
OFF
ON
MUTE
SELECT
SETUP
2
Mounting (4-Post Rackmount)
TheUPSincludesrackmountrailsfor4-postrackmounting.Theusermustdeterminethefitnessofhardwareandproceduresbeforemounting.
Ifhardwareandproceduresarenotsuitableforyourapplication,contactthemanufacturerofyourrackorrackenclosure.Theprocedures
describedinthismanualareforcommonrackandrackenclosuretypesandmaynotbeappropriateforallapplications.
WARNING! The UPS system is extremely heavy. Use caution when lifting and mounting. User must properly stabilize the UPS when
lifting and mounting.
Connectthetwosegmentsofeachshelf
usingtheincludedattachedscrewsand
wing nuts. Leave the screws slightly
loosesothattheshelvescanbeadjusted
inthenextstep.
Adjusteachshelftofityourrack,then
mount them in the lowest available
spaceofyourrackwiththescrews,nuts
and washers provided. Note that the
support ledges should face inward.
Tighten the wingnuts that connect the
shelf segments.
Attach mounting ears to the front
mountingholesofyourUPSusingthe
screwsprovided. The earsshould face
forward.
Usingoneor moreassistants,liftyour
UPS and slide it onto the mounting
shelves.AttachyourUPStotherackby
passingscrews,nutsandwashers(user-
provided)throughitsmountingearsand
intotherackrails.
Mounting (2-Post Rackmount)
If you mount this UPS model in 2-post racks, it requires the addition of a Tripp Lite 2-Post Rackmount Installation Kit (model:
2POSTRMKITWM,soldseparately).SeeInstallationKitowner'smanualforinstallationprocedure.
1
2
3
4
201102170 932611.indd 5 3/30/2011 10:22:11 AM