99
Manual Bypass Operation (for UPS maintenance or replacement)
WARNING! For qualified service personnel only. Failure to follow the bypass procedure completely will not adequately power down
the UPS power/battery module, resulting in the continued risk of death or injury from potential contact with high voltage. The UPS's
power/battery module and detachable PDU are extremely heavy. This procedure requires several people to perform.
TheUPSsystemincludesaself-containedpower/batterymodulealongwithanindependent,detachablePDUwithabypassswitch.Thisswitch
allowsqualifiedservicepersonneltoremovethedetachablePDUfromthepower/batterymoduleforroutinemaintenancewithoutdisrupting
powertoconnectedloads.Whilethis switchissetto “BYPASS”,connectedequipment willreceiveunfilteredACmains power,butthe
equipmentwillnotreceivebatterypowerintheeventofablackout.
Note:AnoptionaldetachablePDUwithhardwireinput/outputisalsoavailableseparatelyfromTrippLite.ContactTrippLitefordetails.
(Optional:Duringahot-swap,thePDUcanbehousedinthebackoftherackconfigurationusingsuppliedPDUhangerbracketsandhardware.
See STEP 1belowformountinginstructions.)
I/P BYPASS
BATTERYAC/DC DC/AC O/P
OFFON
MUTE SELECT
SETUP
UPS Power/Battery Module Removal
STEP 1. (Optional)AttachaPDUhangerbrackettotherightandleftside,rearmountingrailsusingincludedscrewsandcagenuts.
Important:determiningwheretoattachyourPDUhangerbracketswilldependonyourrackconfiguration.Generallyitis
recommendedtomountthebracketsinaUspaceclosetowheretheUPSandPDUaremountedin.Besuretomountbothleftand
rightbracketsinthesameUspaceoneachside.
STEP 2. DisablePowerAlertSoftwareanddisconnectcommunicationcable(s)fromthecommunicationport(s)
A
ontheUPSpower/
batterymodule.
STEP 3. PresstheUPS's“OFF”Button
B
,iftheUPSispowered,untilyouhearabeepandseea"SwitchtoBypassN(NO)/Y(OFF)"
messageshownintheLCDDisplay
C
.Tocontinue,presstheOFFbutton.Ifthebypassvoltageisoutofrange,theunitwill
display"BypassOutofRange,UnabletoBypass"andwillcanceltherequest.Repeatthisprocedure.Iftheerrorpersists,contact
CustomerSupport.
STEP 4. TurnthedetachablePDU'sBypassSwitch
D
to“BYPASS”.
STEP 5. IfanexternalbatterymoduleisconnectedtotheUPS
E
,disconnectitfromtheUPS.
The UPS power/battery module is now safely powered down and it can be detached from the PDU
to perform maintenance/replacement.
STEP 6: RemovethefivescrewsthatholdthedetachablePDUtothepower/batterymodule.
STEP 7: Usingseveralassistantsateachend,carefullypullthedetachablePDUawayfromthepower/batterymodule.Duringthisprocess,
ensurethateachsectionisproperlysupportedaftertheyareseparated.
• Ifthesectionsaredetachedinarackmountapplication,ensurethateachsectionremainsadequatelysupportedbytheUPS's
rackmountrails.RemovetherackmountinghardwarefromthefrontpaneloftheUPS;slidethepower/batterymoduleforward,
andremove.ThePDUwillremainsupportedontherackmountrails.CareshouldbetakeninthisprocessbecausethePDUwill
notbesecuredtotherackwithhardwareofanykind.
•IfitisdesiredtoleavethedetachedPDUintherack,hangtheunitinbackoftherackontheinstalledPDUhangerbracketsby
thescrewsusedtoattachthePDUtotheUPSsystem.
• Ifthesectionsaredetachedinatowerapplication,ensurethatthePDUissupportedbytheUPS'stowerfeet.Adjustthetower
feetsotheyareasclosetogetheraspossible.
To reattach the PDU, reverse the process listed above.
Steps 2, 4 & 5
Step 3
E
D
A
C
B
WARNING! High Voltage! Risk of electrical shock! SEE PAGE 9.