LOCATING STOVE
Proper clearances must be maintained for adequate
air circulation. Adequate ventilation must be
provided while operating this stove.
1. The stove must be placed on solid con-
crete, solid masonry, or on an listed
floor protector, such as Hy-C or Impe-
rial Model UL 5463BK when installed on a
combustible floor. The base must extend at
least 18” beyond the front, rear and sides of the
stove, and must extend under the stove pipe if
it is elbowed towards a wall (see figure 5 and
consult local building codes and fire protection
ordinances.)
2. The stove must have its own flue. DO NOT
CONNECT THIS UNIT TO A CHIMNEY
FLUE SERVING OTHER APPLIANCES.
3. After observing the clearances to combustible
materials (figure 2 – 4), locate your floor
protector accordingly (figure 2) and care-
fully place the stove in your selected location.
Install stove pipe, stove pipe damper, elbows,
and thimble as required, utilizing either a
recently cleaned and inspected 6” masonry
chimney or a 6” i.d. listed chimney. Maximum
64 square inches.
FLOOR
PROTECTOR
DASHED LINE SHOWS
HORIZONTAL CHIMNEY
CONNECTOR AND
ADDITIONAL FLOOR
PROTECTION REQUIRED
BACKWALL
54"
(TOP VIEW)
36"
18"
18"
18"
36"
63"
1
8
"
SIDEWALL
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
COMBUSTIBLE
CONSTRUCTION
ACCORDING TO
NFPA 211
4. Use 6” round black stove pipe. DO NOT use
galvanized duct pipe. Secure pipe sections with
three (3) sheet metal screws in each stove pipe
and/or elbow joint to firmly hold the pipe sec-
tions together. DO NOT CONNECT THIS
STOVE TO ANY AIR DISTRIBUTION OR
DUCT SYSTEM.
5. Re check c learances fr om t he stove,
connector stove pipe, and corner clearances
using the illustrations (figure 2, 3 & 4) and
your local building codes or fire protection
ordinances.
NOTE: Drywall faced with brick or stone must
be considered a combustible surface.
6. DO NOT INSTALL THIS STOVE
IN A MOBILE HOME, TENT OR TRAILER.
(NO EXCEPTIONS)
7. The clearances provided are minimum
dimensions. Installation of this stove must
comply with your local building code rul-
ings.
8. This stove is NOT a UL listed stove.
Continued on next page
Fig. 2 Minimum Clearance Dimensions from Combustible Surfaces Fig. 3
MINIMUM CLEARANCES
TO COMBUSTIBLE SURFACES
Unit to Sidewall ....................................36 inches
Unit to Backwall ...................................36 inches
Unit Corner to Wall ................................36 inches
Pipe Connector to Backwall ......................38 inches
Pipe Connector to Ceiling ........................18 inches
Fig. 4 – Top View
Minimum Corner Clearances from
Combustible Surfaces