Table 13 — Keyboard Directory (cont)
SCHEDULE
Keyboard Entry Display Description
OVRD X Number of hours to extend
occupied mode of schedule 1
PERIOD 1 Define period 1 of time
schedule 1
OCC X Start of occupied time
UNO X Start of unoccupied time
MON X Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)
TUE X Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
WED X Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
THU X Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)
FRI X Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SAT X Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SUN X Sunday flag
HOL X Holiday flag
Time periods 2-8 of schedule 1
(same elements as period 1, schedule 1)
OVRD X Number of hours to extend
occupied mode of schedule 2
PERIOD 1 Define period 1 of time
schedule 2
OCC X Start of occupied time
UNO X Start of unoccupied time
MON X Monday flag (x = entry code)
(1 = yes, .0 or CLR = no)
TUE X Tuesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
WED X Wednesday flag (x = entry code)
(1 = yes, .0 or CLR = no)
THU X Thursday flag (x = entry code)
(1 = yes, .0 or CLR = no)
FRI X Friday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SAT X Saturday flag (x = entry code)
(1 = yes, .0 or CLR = no)
SUN X Sunday flag
HOL X Holiday flag
Time periods 2-8 of schedule 2
(same elements as period 1, schedule 2)
CV — Constant Volume
DX — Direct Expansion
VAV — Variable Air Volume
SERVICE CONFIGURATIONS
Keyboard Entry Display Description
LOG ON Enter password to log on
LOGGEDON Log on okay
When finished with configuration, log off as follows:
LOGGEDON
Shows that configurations are
available
LOG OFF
LOGD OFF
Log off okay; configurations again
password protected
VERSION Software version
XXX-XX-X Software version number
FACT CFG Factory configuration
TYPE X Unit type (0 = CV,1=VAV)
COOL X Cooling (0 = none, 1 = coil)
DXST X
DX cooling stages 0-8
(enter number)
HEAT X
Heating (0 = none,
1 = hot/steam,
2 = electric heat coil)
EHST X
Electric heat stages 0-8
(enter number)
MIXD X
Mixed air damper (0 = none,
1 = yes, 2 = 2-position)
IAQT X Indoor-air quality type
MATP X Mixed air temperature protection
BUS X
Bus number (factory default
set=0)
ADR X
Element address (factory set
default = 1)
PSW X Password XXXX
UNITS X
English/metric system
(0 = English, 1 = metric)
USER CFG User configuration
NTEN X
Nighttime free cooling
configuration
HUEN X Humidity configuration
OHEN X Occupied heating configuration
RSEN X
Space temperature reset
configuration
DLEN X Demand limiting configuration
FTEN X Fan tracking configuration
OAEN X Constant outside air
NPEN X Night purge
AQEN X Indoor air quality
IAQP X Indoor air quality priority level
OSEN X Optimal start/stop configuration
TSCH X Timed override schedules
TOVR X Timed override values
HEATCOIL Configuration of heating coil
MPG X Master proportional gain
MIG X Master integral gain
MDG X Master derivative gain
SMG X Submaster gain
SCV X Submaster center value
FOV X Fan off value
SMR X Submaster reference value
SMR X Submaster reference value forced