UNIT 24 VAC (R)
Y2
R
C
2-SPEED
AIR CONDITIONER
(38TD)
Yellow
Red
Blue
White
Brown
Green
Orange
Black
COOL 1 (Y1)
COOL 2 (Y2)
HEAT 1 (W1)
HEAT 2 (W2)
FAN (G)
RV-COOL (O)
RV-HEAT (O)
OR
VARIABLE SPEED
FURNACE
COMFORT ZONE CENTER
W
G
C
R
Y
Y1
L
RELAY
COIL
Green
(P5)
CONNECTION AT
CONTROL BOARD
Black
13
E
(KGATT0101VSP)
NOTE: Put set-up switch No. 2
at the control board to
the ON position (up)
when using Two Stage
Relay Kit
KGATT0101VSP
Accessory (Optional).
A94037
UNIT 24 VAC (R)
C
R
Y1
L
2-SPEED
AIR CONDITIONER
(38TD)
Yellow
Red
Blue
White
Brown
Green
Orange
Black
COOL 1 (Y1)
COOL 2 (Y2)
HEAT 1 (W1)
HEAT 2 (W2)
FAN (G)
RV-COOL (O)
RV-HEAT (O)
OR
FURNACECOMFORT ZONE CENTER
G
W
Y2
H
R1
Y
R
R1 = Relay DPST, Pilot Duty,
24-v coil (HN61KK324) or Equivalent.
H = Humidistat, opens on humidity
rise (HL38MG026)
C
Latent Capacity Control (LCC)
F
A94038
UNIT 24 VAC (R)
C
R
Y1
L
2-SPEED
AIR CONDITIONER
(38TD)
Yellow
Red
Blue
White
Brown
Green
Orange
Black
COOL 1 (Y1)
COOL 2 (Y2)
HEAT 1 (W1)
HEAT 2 (W2)
FAN (G)
RV-COOL (O)
RV-HEAT (O)
OR
FURNACECOMFORT ZONE CENTER
G
Y2
H
R1
R
R1 = Relay DPST, Pilot Duty,
24-v coil (HN61KK324) or Equivalent.
H = Humidistat, opens on humidity
rise (HL38MG026)
W
C
Y
Latent Capacity Control (LCC)
G
A94039
UNIT 24 VAC (R)
R
2-SPEED
AIR CONDITIONER
(38TD)
Yellow
Red
Blue
White
Brown
Green
Orange
Black
COOL 1 (Y1)
COOL 2 (Y2)
HEAT 1 (W1)
HEAT 2 (W2)
FAN (G)
RV-COOL (O)
RV-HEAT (O)
OR
FURNACECOMFORT ZONE CENTER
Y1
L
H
W2
R
C
Y/Y2
W/W1
G
NOTE: Locking furnace into "low fire" may help prevent over conditioning
in the heating mode. This will allow the furnace to stage between
low and high fire. Before using this feature read furnace Installation
Instructions for two-stage operation. Connect "W2" from the
Comfort Zone Center to "W2" on the furnace control board.
See Furnace Installation Instructions For Details Involving
Set-Up Switch Configuration and Two-Stage Furnace Operation.
Y2
C
A94040
Fig. 20—Typical Wiring Diagrams (Furnace with Air Conditioner) Continued
25