9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev C www.powerware.com
21
10. Verify that the input circuit breaker is in the OFF position (see
Figure 12).
11. Remove the input isolation transformer wiring access cover and
retain.
Battery Circuit Breaker
Input Circuit Breaker
Input Isolation
Transformer
Wiring Access Cover
Figure 12. UPS with Input Isolation Transformer Rear View
12. Hardwire the input, output, and ground terminations for the UPS or
input isolation transformer. See Table 1 for wiring specifications.
For a detailed view of the terminal block, see Figure 13 or Figure 14
on page 23.