COMMUNICATION
EATON Powerware
®
9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev C www.powerware.com
58
To install an RMP:
NOTE If mounting to a hollow wall, secure the enclosure bottom to a wood or metal stud
within the wall. Do not use hollow wall anchors. The RMP can also be mounted to a single-
or double-gang electrical box.
1. If wall mounting, securely mount the RMP. Continue to Step 2.
If desk mounting, install the provided bumpers to the bottom of the
RMP enclosure. Proceed to Step 3.
2. Install 1/2” conduit from the RMP to the IRC through the cable exit
openings (see Figure 42). Proceed to Step 4.
3. Install wiring from the RMP to the IRC using the cable listed in
Table 4 and the provided strain relief bushings in the cable exit
openings in the IRC (see Figure 44) and the RMP.
4. Connect the wiring between the RMP and the IRC plug-in terminal
blocks using terminations shown in Table 4. See Figure 43 and
Figure 44 for plug-in terminal block locations.
Table 4. RMP Wire Terminations
From RMP Terminal To IRC Terminal Remarks
J1-1 J1-1
J1-3 J1-3
J1-4 J1-4
Use Beldon 8690 060 or
J1-5 J1-5
equ
va
en
ca
e
J1-6
J1-6
5. Install the IRC into an open X-Slot communication bay (see
page 50).