OPERATION
EATON Powerware
®
9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev C www.powerware.com
78
UPS Shutdown
To shut down the UPS:
1. Press any button on the front panel display to activate the menu
options.
2. Press the
button on the front panel display and then press the
button to select the TURN UPS ON/OFF menu.
3. Press the
button to select the TURN UPS OFF option.
4. Press and hold the
button for three seconds, until the UPS stops
beeping.
The UPS stops supplying power to the load.
5. Switch the UPS battery circuit breaker to the OFF position.
The UPS disconnects from the batteries and is on logic power only.
6. Switch off utility power where the UPS is connected.