UPS SETUP
EATON Powerware
®
9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev C www.powerware.com
10
Floor Loading
When planning the installation, consider the UPS weight for floor
loading. The strength of the installation surface must be adequate for
point and distributed loadings. The approximate weights are shown in
the following table.
Standard Model Floor Loadings (2-High/3-High Cabinets)
Powerware 9355
Maximum
Weight
Point Loading
lb/in
2
(kg/cm
2
)
2-High UPS 381 lb (173 kg) 95 (6.7)
3-High UPS-32 587 lb (266 kg) 147 (10.3)
3-High UPS-64 619 lb (281 kg) 155 (10.9)
2-High EBM 480 lb (218 kg) 120 (8.4)
3-High EBM 710 lb (322 kg) 178 (12.5)
Clearances
The following clearances are recommended for the Powerware 9355
UPS:
From Front of Cabinet 36” (91.4 cm) working space
From Back of Cabinet 6” (15.2 cm) without PDM installed; with PDM installed,
clearance determined by customer-supplied mating plug