9355 UPS (10/15 kVA) User’s Guide S 164201594 Rev C www.powerware.com
59
6. To check the operation of the RMP, ensure that the UPS is
supplying the load via the inverter or bypass. If the indicators on the
RMP show the appropriate status, then it is operating correctly.
If the RMP is not operating correctly, check the wiring, the fuse on
the IRC, and the plug-in terminal blocks for proper seating. If all
connections are secure but the RMP still does not operate
correctly, replace the fuse. If this does not correct the problem,
contact your service representative for verification that the RMP is
working correctly.
Plug-in Terminal Block J1
to Industrial Relay Card
NOTE Conduit and wiring
supplied by the customer. The
maximum distance between
the RMP and the UPS is not to
exceed 152.4m (500 ft).
Figure 43. RMP Top Internal View