Wall Sleeve Installation Instructions (PXWS)
NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and accessories.
If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read these instructions
completely before attempting installation.
For Deep Wall Installation See Section II
The following instructions apply ONLY to walls less than
13 1/4" in depth.
1. From inside the building, position the wall sleeve in the opening
and push it through the wall so it protrudes at least 1/4" on the
outside, note Figure 5.
2. Position the wall sleeve with a slight tilt towards the outside to
facilitate condensate drainage. It should be level side-to-side
and the front should be 1/4 bubble higher than the back. DO
NOT allow any pitch toward the inside.
Electrical shock hazard.
Turn electric power OFF at the fuse box or service panel
before making any electrical connections and ensure a
proper ground connection is made before connecting line
voltage. Failure to do so can result in property damage,
personal injury and/or death.
Typical Wall Sleeve Installation
Figure 5
42"
(107.3 cm) min.
50" (127 cm) mi
n.
10"
(25.4 cm)
max.
16 "
(41.3 cm)
13
"
(34.9 cm)
Lintel to support masonry walls
Electrical receptacle
Wall opening
Wall sleeve
Insulation
Smooth side of screw
clip facing into room
Electrical receptacle
Insulation