ACC-SVN100A-EN • LonTalk Communication Interface 11
Software Installation
Figure 2. Start software installation procedure with Tracer TU to the LCI-C LLID
1. Connect the laptop containing Tracer TU to the external USB port (A) on the control
panel, which is directly connected to the UC800 (B) inside the panel.
2. Click on the Tracer TU icon and the Connect screen appears.
3. Select Direct Connection (via USB cable) and click Connect. The Tracer TU
Equipment Utility screen appears as shown in Figure 2.
4. Click the Configuration tab.
Note: If the BAS interface is already configured with the LCI-C LonTalk™ Extension,
proceed to step 6 or proceed with step 5 to configure.
5. To configure the LCI-C LonTalk Extension, click on the Options expanding box and
select the interface.
6. Click Save and the Binding tab appears as shown in Figure 3, p. 12.
7. Select the device to bind from the binding list on the LLID Binding screen.
8. Click Bind and the Select device with magnet screen appears.
Equipment Utility Screen