A SERVICE OF

logo

ACC-SVN100A-EN • LonTalk Communication Interface 25
Network Variable and Configuration Property
Definitions
This section includes:
Network variable input definitions
Network variable output definitions
Configuration property definitions
Network Variable Input Definitions
The network variable input definitions are listed alphabetically by network variable.
nviBaseLdgReq
Base loading Auto/On request, SNVT_switch
This input requests the chiller to use the base loading control method. With this method,
the chiller controls to a requested capacity level rather than to a chilled-water or hot-water
setpoint. This variable is used as an Auto/On and cannot be used to force the chiller to
exit base loading control.
Default: Uses nciBaseLdgReq
Invalid value: 0xFF, 0xFF
nviBaseLdgSetpt
Base loading setpoint, SNVT_lev_percent
This input network variable is the requested capacity level the chiller should control to
when using the Base Loading control method. Any setpoint value received will be
clamped into a valid range by the chiller.
Default: Uses nciBaseLdgSetp
Invalid value: 0x7FFF = 163.835%
Range: -163.84% to 163.83% (limited at chiller) or invalid
Valid range (uses 2-state definition of SNVT_switch)
Value
byte
State byte
Resulting
interpretation
Any 0 Auto (0)
01 Auto (0)
>0 1 On (1)
Any 0xFF Invalid