22 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variables- Alphabetically
Network variables for the LCI-C Extension are listed alphabetically in Table 1 with
columns for chillers types.
Not all variables are available for every chiller. For example, the variables
nvoAirFlowPctC1 and nvoCondFans apply to other chiller models that use the LCI-C
extension.
Table 4. Network variables for the LCI-C Extension, listed alphabetically
Variable name SNVT
CVH/CVG
Tracer
UC800
nviBaseLdgReq SNVT_switch(95) ×
nviBaseLdgSetpt SNVT_lev_percent(81) ×
nviCapacityLim SNVT_lev_percent(81) ×
nviChillerEnable SNVT_switch(95) ×
nviCoolSetpt SNVT_temp_p(105) ×
nviHeatSetpt SNVT_temp_p(105) ×
nviMode SNVT_hvac_mode(108) ×
nviNoiseRdcnReq SNVT_switch(95)
nviRequest.RQ_Clear_Alarm SNVT_obj_request(92) ×
nvoActiveBLSetpt SNVT_lev_percent(81) ×
nvoActiveSetpt SNVT_temp_p(105) ×
nvoActualCap SNVT_lev_percent(81) ×
nvoAirFlowPctC1 SNVT_lev_percent(81)
nvoAirFlowPctC2 SNVT_lev_percent(81)
nvoAlarmDescr SNVT_str_asc(36) ×
nvoCapacityLim SNVT_lev_percent(81) ×
nvoChillerStat.chlr_op_mode SNVT_chlr_status(127) ×
nvoChillerStat.chlr_run_mode SNVT_chlr_status(127) ×
nvoChillerStat.chw_flow SNVT_chlr_status(127) ×
nvoChillerStat.condw_flow SNVT_chlr_status(127) ×
nvoChillerStat.in_alarm SNVT_chlr_status(127) ×
nvoChillerStat.limited SNVT_chlr_status(127) ×
nvoChillerStat.local SNVT_chlr_status(127) ×
nvoChillerStat.run_enabled SNVT_chlr_status(127) ×
nvoCondControl SNVT_lev_percent(81)
nvoCondFans SNVT_state(83)
nvoCondRfgtPrsC1 SNVT_press_f(59) ×
nvoCondRfgtPrsC2 SNVT_press_f(59) ×
nvoCondRfgtPrsC3 SNVT_temp_f(105)
nvoCondRfgtPrsC4 SNVT_temp_f(105)
nvoCondRfgtTmpC1 SNVT_temp_p(105) ×
nvoCondRfgtTmpC2 SNVT_temp_p(105) ×
nvoCondRfgtTmpC3 SNVT_temp_p(105)