30 LonTalk Communication Interface • ACC-SVN100A-EN
Network Variable and Configuration Property Definitions
nvoActualCap
Actual running capacity, SNVT_lev_percent
This network variable provides the level of capacity at which the chiller is currently
operating. It may be more or less than the nominal value of the chiller’s capacity.
Default: 0x7FFF = 163.835%
Invalid value: 0x7FFF = 163.835%
nvoAirFlowPctC1
Air flow percent—circuit 1, SNVT_lev_percent
This network variable provides the approximate air flow percentage of circuit 1.
Default: 0x7FFF = 163.835%
Invalid value: 0x7FFF = 163.835%
nvoAirFlowPctC2
Air flow percent—circuit 2, SNVT_lev_percent
This network variable provides the approximate air flow percentage of circuit 2.
Default: 0x7FFF = 163.835%
Invalid value: 0x7FFF = 163.835%
nvoAlarmDescr
Alarm description, SNVT_str_asc
This network variable provides alarm messages based on manufacturer-determined
criteria. Alarm text will vary significantly based on the chiller model. See the
corresponding chiller literature for more details on the diagnostics. The format will be as
follows: “s nnnnnnnnnnnnnnnnnnnnnnnnnnnnn”
s Indicates the severity of the diagnostic. There are five possibilities. There is an
ASCII space between s and the first n.
P = normal, last reset resulted from a power up
0 = normal, last reset was not from power up
1 = informational message (handle at next scheduled routine maintenance)
2 = service required (handle at normal rates during normal working hours)
3 = critical alarm (handle now, cost is no object)
n Represents 29 ASCII characters that form the human readable message. The last
n must be null (0x00). Can be less than 29 ns, but not more.
For 0 or P this text must be Normal
When transmitted: It is transmitted when a diagnostic occurs
Update rate: Update occurs no faster than the configured min send time