ACC-SVN100A-EN • LonTalk Communication Interface 41
Network Variable and Configuration Property Definitions
nvoOilTempX
Oil temperature—compressor X,* SNVT_temp_p
nvoOilTempA
nvoOilTempB
nvoOilTempC
nvoOilTempD
nvoOilTempE
nvoOilTempF
This network variable provides the temperature of the oil in the compressor X (*where
X is A, B, C, D, E, or F depending on the network variable.) There are separate network
variables for each compressor.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
nvoOnOff
Chiller running state, SNVT_switch
This variable indicates whether the chiller is on (currently doing either cooling or heating)
or is considered off (currently doing neither cooling nor heating)
nvoOutdoorTemp
Outdoor air temperature, SNVT_temp_p
This network variable provides the temperature of the outdoor air.
Default: 0x7FFF = 327.67°C
Invalid value: 0x7FFF = 327.67°C
Valid range (uses 2-state definition of SNVT_switch)
Value
byte
State byte Resulting interpretation
00Off (0)
100 1 On (1)
0xFF 0xFF Invalid